drop shadow left
Field's Fire Protections Inc.
drop shadow right
 
Fields Fire Store

Special Hazard, Ecaro-25, FM 200, ProInert, CO2, Water Mist

There are many different types of special hazard fire suppression systems.  Special Hazards can be defined as any fire hazard that needs special attention and innovation to extinguish the fire.  Field's Fire Protection, Inc. distributes Fike Special Hazard Fire Suppression Systems including Ecaro-25, FM-200, ProInert, High Pressure Carbon Dioxide, and Water Mist.

Special Hazard Definitions

Clean Agent – Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. 

Halocarbon Agent – An agent that contains as primary components one or more organic compounds containing one or more of the elements fluorine, chlorine, bromine, or iodine.

High Pressure – Indicates that the carbon dioxide is stored in pressure containers at ambient temperatures.  At 70F, the pressure in this type of storage is 850 psi.

Inert Gas Agent – An agent that contains as primary components one or more of the gases helium, neon, argon, or nitrogen.  Inert gas agents that are blends of gases can also contain carbon dioxide as a secondary component.

Local Application – A system consisting of a supply of extinguishing agent arranged to discharge directly on the burning material.

Lowest Observable Adverse Effect Level (LOAEL) – The lowest concentration at which an adverse physiological or toxicological effect has been observed.

No Observed Adverse Effect Level (NOAEL) – The highest concentration at which no adverse toxicological or physiological effect has been observed.

Total Flooding – The act and manner of discharging an agent for the purpose of achieving a specified minimum agent concentration throughout a hazard volume.

 

ECARO-25 

               

Agent

The extinguishing agent used in Fike ECARO-25 Suppression Systems is Pentafuoroethane -- more commonly known by its ASHRAE designation: HFC-125.

HFC-125 is a colorless, odorless, liquefied compressed gas.  (See Physical Properties Table below.)  It is stored as a liquid, but is dispensed into the hazard as a colorless, electrically-nonconductive, gaseous vapor due to its relatively low boiling point.

HFC-125 has been tested and verified to be safe for use in occupied spaces when used as specified in the U.S. EPA Significant New Alternative Policy (SNAP) rules.  Tests have proven that exposure to HFC-227ea (FM-200) is safe and effective in extinguishing fires at low concentrations; most of which are well below the EPA's maximum exposure levels.  HFC-125 is approved for use in occupied areas up to a 11.5% concentration by volume with mandated egress time of five minutes or less.

Performance

HFC-125's mechanism of extinguishing fires is considered active.  Its primary action is through physically cooling the fire at the molecular level.  HFC-125 belongs to the same class of agents used in refrigeration and is an efficient heat transfer agent.  HFC-125 removes the thermal energy from the fire to the extent where the combustion reaction cannot sustain itself.

Additionally, there is a chemical action that provides a secondary means of extinguishing the fire.  Trace amounts of free radicals are released into the fire -- thereby inhibiting the chain reaction of combustion.

HFC-125 does not significantly reduce oxygen levels and is safe for use in occupied spaces in accordance with the U.S. EPA guidelines.  HFC-125 can be removed from the protected space by simple means of ventilation after discharge.

Chemical Name Pentaflouroethane
Chemical Formula CHF2CF3
CAS No. 354-33-6
Molecular Weight 120.02
Boiling Point, 1 atm -54.7F
Freezing Point -153F
Critical Temperature 151.25F
Critical Pressure 526.6 psia
Critical Density 35.70 lb/ft3
Vapor Density @ 77F .3111 lb/ft3
Ozone Depletion Potential 0.0
Global Warming Potential 2800 GWP

Use and Limitations

Fike ECARO-25 Systems must be designed and installed in accordance with the requirements outlined in this manual, and in accordance with the requirements of the Standard for Clean Agent Extinguishing Systems, NFPA 2001, latest edition.  ECARO-25 systems are primarily used to protect hazards that are enclosed; this provides a means to establish and maintain an effective extinguishing concentration.  Typical hazards that can be protected include the following.

  • Electrical and electronic hazards.
  • Telecommunications facilities.
  • Storage Rooms -- Flammable liquids and gases.
  • High value assets, where the associated down-time would be costly.

ECARO-25 systems shall not be used on fires involving the following materials.

  • Chemicals or mixtures of chemicals that are capable of rapid oxidation in the absence of air.  Examples include Cellulose Nitrate and Gunpowder.
  • Reactive metals such as Lithium, Sodium, Potassium, Magnesium, Titanium, Zirconium, Uranium, and Plutonium.
  • Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride.
  • Chemicals capable of undergoing auto-thermal decomposition.  Examples include Organic Peroxides and Hydrazine.

Exposure

Although HFC-125 is considered to be non-toxic, the EPA has established the guidelines controlling the amount (concentration) of agent provided for the protected area.  Based on PBPK modeling, the EPA allows HFC-125 for use where people are normally present (normally occupied spaces) up to concentration of 11.5% by volume with exposure limited to 5 minutes or less.

WARNING: The discharge of clean agent systems to extinguish a fire can result in potential hazard to personnel from the natural form of the clean agent or from the products of combustion that result from exposure of the agent to the fire or hot surfaces.  Unnecessary exposure of personnel either to the natural agent or to the products of decomposition shall be avoided.

The requirements for pre-discharge alarms and time delays are intended to prevent unnecessary exposure to humans where their presence is not critical to the operation of the area being protected.  Suitable safeguards shall be provided to ensure prompt evacuation of (and prevent entry into) protected areas after discharge.

Exposure Limits

Normally Occupied Areas.  ECARO-25 systems can be designed to concentrations above the NOAEL, given that means be provided to limit exposure to design concentrations shown in the table below that correspond to a maximum permitted human exposure time of five minutes.

HFC-125 Concentration Parts Per Million (ppm) Human Exposure Time (minutes)
7.5% 75,000 5.00
8.0% 80,000 5.00
8.5% 85,000 5.00
9.0% 90,000 5.00
9.5% 95,000 5.00
10.0% 100,000 5.00
10.5% 105,000 5.00
11.0% 110,000 5.00
11.5% 115,000 5.00
12.0% 120,000 1.67
12.5% 125,000 0.59
13.0% 130,000 0.54
13.5% 135,000 0.49

Not Normally Occupied Spaces.  ECARO-25 systems can be designed for concentrations exceeding the LOAEL provided that any personnel in the area can escape within 30 seconds.

NOTE: Fike does not recommend ECARO-25 systems to be used in any normally occupied spaces where the design concentration required is above 11.5%

Toxicity

With a database in excess of 70 toxicity tests, ECARO-25 has been extensively tested and approved by institutions and agencies around the world.  The LC50 toxicity rating for ECARO-25 is greater than 700,000 ppm.  When you consider that most ECARO-25 systems are designed for concentrations providing 80,000 ppm or less, it is evident that ECARO-25 is safe to use.

ECARO-25 will decompose to form halogen acids when exposed to extremely high temperatures.  The formation of these acids is minimized by using fast-acting Fike detection and control systems and proper system design and installation of piping system to deliver the agent quickly.  The generation of by-products from ECARO-25 discharge will be minimal when properly applied.

Information provided from Fike ECARO-25 System Manual Rev. 5/05

FM-200

Agent

FM-200 is a clean agent extinguishing agent. The chemical name of FM200 is Heptafluoropropane -- more commonly known by its ASHRAE designation: HFC227ea.

HFC-227ea is a colorless, odorless, liquefied compressed gas.  (See Physical Properties Table below.)  It is stored as a liquid, but dispensed into the hazard as a colorless, electrically-nonconductive, gaseous vapor due to its relatively low boiling point.

HFC-227ea has been tested and verified to be safe for use in occupied spaces when used as specified in the U.S. EPA Significant New Alternative Policy (SNAP) rules.  Tests have proven that exposure to HFC-227ea is safe and effective in extinguishing fires at low concentrations; most of which are well below the EPA's maximum exposure levels.  HFC-227ea is approved for use in occupied areas up to a 10.5% concentration by volume with mandated egress time of five minutes.

Performance

HFC-227ea's mechanism of extinguishing fires is considered active.  Its primary action is through physically cooling the fire at the molecular level.  HFC-227ea belongs to the same class of agents used in refrigeration and as such, is an efficient heat transfer agent.  HFC-227ea removes the thermal energy from the fire to the extent where the combustion reaction cannot sustain itself.

Additionally, there is a chemical action that provides a secondary means of extinguishing the fire.  Trace amounts of free radicals are released into the fire -- thereby inhibiting the chain reaction of combustion.

HFC-227ea does not significantly reduce oxygen levels and is safe for use in occupied spaces in accordance with the U.S. EPA guidelines.  HFC-227ea can be removed from the protected space by simple means of ventilation after discharge.

Physical Properties of HFC-227ea

Chemical Name 1,1,1,2,3,3,3 - Heptafluoropropane
Chemical Formula CF CHFCF
CAS No. 431-89-0
Molecular Weight 107.30
Boiling Point, 1 atm -15.9F
Freezing Point -204F
Flammable Limits nonflammable
Critical Temperature 214.9F
Critical Pressure 424.7 psia
Critical Density 38.77 lb/ft3
Liquid Density @ 77F 86.53 lb/ft3
Vapor Density @ 77F and 1 atm .4462 lb/ft3
Ozone Depletion Potential 0.0
Global Warming Potential 2900 GWP
Atmospheric Lifetime 36.5 years

Use and Limitations

Fike HFC-227ea Systems must be designed and installed in accordance with the requirements outlined in this manual, and in accordance with the requirements of the Standard for Clean Agent Extinguishing Systems, NFPA 2000, latest edition.  HFC-227ea systems are primarily used to protect hazards that are enclosed; this provides a means to establish and maintain an effective extinguishing concentration.  Typical hazards that can be protected include the following:

  • Electrical and electronic hazards.
  • Telecommunications facilities.
  • Storage Rooms -- Flammable liquids and gases.
  • High value assets, where the associated down-time would be costly.

HFC-227ea systems shall NOT be used on fires involving the following materials.

  • Chemicals or mixtures of chemicals which are capable of rapid oxidation in the absence of air.  Examples include Cellulose Nitrate and Gunpowder.
  • Reactive metals such as Lithium, Sodium, Potassium, Magnesium, Titanium, Zirconium, Uranium, and Plutonium.
  • Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride.
  • Chemicals capable of undergoing auto thermal decomposition.  Examples include Organic Peroxides and Hydrazine.

(Source: NFPA 2001, Section 1)

Exposure

Although HFC-227ea is considered to be non-toxic, the EPA has established the guidelines controlling the amount (concentration) or agent provided for the protected area.  Based on PBPK modeling, the EPA allows HFC-227ea for use where people are normally present (normally occupied spaces) up to concentration of 10.5% by volume with exposure limited to 5 minutes.

WARNING: The discharge of clean agent systems to extinguish a fire can result in potential hazard to personnel from the natural form of the clean agent or from the products of combustion that result from exposure of the agent to the fire or hot surfaces.  Unnecessary exposure of personnel either to the natural agent or to the products of decomposition shall be avoided.

The requirement for pre-discharge alarms and time delays are intended to prevent unnecessary exposure to humans where their presence is not critical to the operation of the area being protected.  Suitable safeguards shall be provided to ensure prompt evacuation of (and prevent entry into) protected areas after discharge.

Exposure Limits

HFC-227ea systems provided for Normally Occupied Spaces can be designed for concentrations above to the NOAEL level of 9% by volume, given that means be provided to limit exposure to design concentrations shown in the table below that correspond to a maximum permitted human exposure time of five minutes.

HFC-227ea Concentration Parts Per Million (ppm) Human Exposure Time (minutes)
9.0% 90,000 5.00
9.5% 95,000 5.00
10.0% 100,000 5.00
10.5% 105,000 5.00
11.0% 110,000 1.13
11.5% 115,000 0.60
12.0% 120,000 0.49

HFC-227ea systems provided for Normally Non-Occupied Spaces can be designed for concentrations in excess of the LOAEL concentration of 10.5%.  Where a possibility exists for personnel to be exposed, means shall be provided to limit exposure times in accordance with the above table.  In the absence of the information needed to fulfill the conditions listed above, the following provisions shall apply.

  • Where egress takes longer than 30 seconds but less than 1 minute, the HFC-227ea system shall not be designed for a concentration exceeding the LOAEL of 10.5% by volume.
  • Where egress takes less than 30 seconds, the HFC-227ea system can be designed for a concentration that exceeds the LOAEL of 10.5% by volume.

Toxicity

With a database in excess of 70 toxicity tests, HFC-227ea has been extensively tested and approved by institutions and agencies around the world.  The LC50 toxicity rating for HFC-227ea is greater than 800,000 ppm.  when you consider that most HFC-227ea systems are designed for concentrations providing 105,000 ppm or less, it is evident that HFC-227ea is safe to use.

HFC-227ea will decompose to form halogen acids when exposed to extremely high temperatures. The formation of these acids is minimized by using fast-acting Fike detection and control systems, and proper system design and installation of the piping system to deliver the agent quickly.  The generation of by-products from the HFC-227ea discharge will be minimal when properly applied.

Information provided from FIKE HFC-227ea System Manual Rev. 6/06

ProInert

Agent

The extinguishing agent used in Fike's ProInert Fire Extinguishing System is a 50%-50% blend of Nitrogen and Argon -- more commonly known by its ASHRAE designation: IG-55.  Because both Nitrogen and Argon occur naturally in the atmosphere, the Ozone depleting factor is zero.  The Global Warming effect is zero and the Atmospheric Lifetime is not a factor.

The agent is stored in Fike high-pressure cylinders at a maximum pressure of 2,900 psi at 60F.  When discharged, IG-55 requires little or no clean-up, making it especially attractive for use in applications where damage from other extinguishing methods would be prohibitive.

Performance

IG-55 extinguishes a fire by reducing the residual oxygen concentration to a level that will no longer support combustion.  IG-55 is most effective when utilized in Total Flooding applications where the protected hazard is enclosed or for protection of equipment that is self-enclosed in order to maintain the agent concentration after discharge.

Because IG-55 does not decompose measurably when extinguishing a fire, there are no toxic or corrosive decomposition products found, other than those that may have been released due to the effects of the fire on the materials within the enclosure.  A typical IG-55 Total Flood system is designed to provide a residual oxygen level of between 10% and 15% after discharge.  While the residual oxygen level will not support combustion of most fires, personnel within the space will still be able to breathe normally, allowing sufficient time for egress, providing there are no harmful decomposition products from the materials affected by the fire itself.

IG-55 can be removed from the protected space by simple means of ventilation after the discharge.

Physical Properties

IG-55 is a clear, electrically non-conductive gas that when discharged leaves no residue and does not result in "fogging" of the hazard.  IG-55 is relatively odorless; however, some odor may be detected after flame extinguishment due to decomposition products from the materials affected by the fire.  Complete listing of physical and chemical properties of IG-55 are listed below.

Chemical Name N2/Ar
Molecular Weight 33.95
Boiling Point at 760 mm Hg -310.2F
Critical Pressure 602 psia
Critical Temperature -210.5F
Relative Density compared to air 1.18

Use and Limitations

ProInert Fire Extinguishing Systems must be designed and installed in accordance with the requirements outlined in the manual, and in accordance with the requirements of latest editions of NFPA 2001 and other applicable standards.  Other countries and insurance organizations may have differing requirements.  ProInert Fire Extinguishing Systems are used to protect hazards that are enclosed and described as Total Flooding; this provides a means to establish and maintain an effective extinguishing concentration.

Typical hazards that can be protected include the following:

  • Electrical and electronic hazards.
  • Telecommunications facilities.
  • Storage Rooms -- Flammable liquids and gases.
  • Sub floors and other concealed spaces.
  • High value assets, where the associated down-time would be costly.

ProInert Fire Extinguishing Systems shall NOT be used on fires involving the following materials:

  • Chemicals or mixtures of chemicals that are capable of rapid oxidation in the absence of air.  Examples include Cellulose Nitrate and Gunpowder.
  • Reactive metals such as Lithium, Sodium, Potassium, Magnesium, Titanium, Zirconium, Uranium, and Plutonium.
  • Metal hydrides such as Sodium Hydride and Lithium Aluminum Hydride.
  • Chemicals capable of undergoing auto thermal decomposition.  Examples include Organic Peroxides and Hydrazine.

Exposure

Although IG-55 is composed of gases that occur naturally in the atmosphere and is considered to be non-toxic, the following guidelines have been established regarding human exposure.  These guidelines are defined as follows (extracted from NFPA 2001)

  • Inert gas systems designed to a concentration below 43% (corresponding to an oxygen concentration of 12%, sea level equivalent of oxygen) shall be permitted, where means are provided to limited exposure to no longer than 5 minutes.
  • Inert gas systems designed to concentration between 43 and 52% (corresponding to between 12% and 10% oxygen, sea level equivalent of oxygen) shall be permitted, where means are provided to limited exposure to no longer than 3 minutes.
  • Inert gas systems designed to concentration between 52 and 62% (corresponding to between 10% and 8% oxygen, sea level equivalent of oxygen) shall be permitted given the following:

                         (a)  The space is normally occupied

                         (b)  Where personnel could possibly be exposed, means are provided to limit the exposure to less

                                than 30 seconds.

  • Inert gas systems designed to concentration above 62% (corresponding to 8% oxygen or below, sea level equivalent of oxygen) shall only be used in unoccupied areas where personnel are not exposed to such oxygen depletion.

WARNING:  Unnecessary exposure of personnel to the heat or by-products produced by the products affected by the fire should be avoided.

WARNING:  For risks that are occupied, ensure that the system is designed such that exposure of personnel to agent concentration is within the limits specified above.

Pre-discharge alarms and time delays are intended to prevent unnecessary exposure to humans where their presence is not critical to the operation of the area being protected.  Suitable safeguards shall be provided to ensure prompt evacuation of (and prevent entry into) protected areas after discharge.  Safety devices, such as warning signs, audible devices, self-contained breathing apparatus, evacuation plans and personnel training shall be considered where applicable.

Pre-discharge alarms and evacuation drills shall be provided for areas where the design concentration results in a residual Oxygen level of less than 10%.

Information provided from FIKE ProInert Manual.

High Pressure Carbon Dioxide

Agent

CO2 is an odorless, colorless, electrically non-conductive, non-corrosive, and non-deteriorating inert suppression agent. It is approximately 50% heavier than air, and is normally present in the atmosphere at about 0.03% by volume. CO2 is instrumental in controlling respiration and other vital responses in animals and humans, but it WILL NOT support life.

Usage Limitations and Personnel Safety Recommendations

CO2 is a standard commercial product commonly used for carbonating beverages, fast-freezing food products, purging pipes and tanks, medical purposes, and a multitude of additional tasks. It is also used for fire fighting purposes: i.e. hose reels, portable hand extinguishers, and engineered fixed pipe systems. CO2 is available in most large cities and seaports throughout the world. 

CO2 extinguishes fire by reducing the oxygen content of the protected space and/or local flame front to a point where it will not support combustion. Oxygen reduction below 16% by volume will extinguish most fires. Surface or “flash” type fires (oils, paints, etc.) are quickly extinguished. Deep-seated or “smoldering” type fires (paper, baled cotton, clothing, etc.) are extinguished by the prolonged action of a high concentration of CO2. Retaining the agent within the protected space reduces the fire’s ability to re-ignite. In addition, CO2 has a cooling effect on the surrounding atmosphere that has been found to be a benefit to fire extinguishment.

Storage and Pressure

When used as a fire-fighting agent, CO2 is stored under pressure in a liquid/vapor state. There are two forms of CO2 storage: Low Pressure, using a refrigerated storage tank, and High Pressure, using spun-steel cylinders of smaller capacities. Fike systems utilize high-pressure storage cylinders containing CO2 at an internal pressure of 850 psig (5861 kPa) when stored at an ambient temperature of 70ºF (21ºC).


Temperature

The temperature of liquid CO2 is approximately –110ºF. (-78.8ºC.) as it is discharged from a nozzle. Direct contact with the liquid agent being discharged from the nozzle(s) will have a freezing effect on objects within the hazard and can cause frostbite and/or freezing if contact is made with the skin. The liquid phase of the agent vaporizes quite rapidly when coming into contact with the atmosphere, thus limiting this hazard to the immediate vicinity of the nozzle.

Visibility

The discharge of CO2 resembles a cloud as liquid agent vaporizes. The low temperature of the agent chilling the moisture in the atmosphere causes this cloud effect, or fogging. The fine “snow” accompanying the discharged liquid is remnant particles of “dry ice”.

Noise


The high pressure/velocity discharge from the system nozzles(s) can cause noise loud enough to be startling, but is ordinarily insufficient to cause traumatic injury.

Cleanup


CO2 vaporizes completely after discharge; whereas the cost of clean-up and peripheral damage associated with water sprinkler systems, foam systems, and dry chemical agents can exceed the cost of the actual fire damage itself. Therefore, the cleanup costs and downtime associated with a CO2 system discharge are negligible. CO2 is an inert gas and most materials or equipment are totally unaffected by exposure to the agent. It is stable, even at high temperatures, and does not decompose when subjected to open flame or extreme temperatures; therefore, CO2 does not cause metals to deteriorate or corrode.

Use and Limitations


CO2 systems can be used on Class “A” fires involving wood, paper, cloth, or any product that leaves a carbon ash when it burns. Class “B” fires involving flammable liquids or vapors, and Class “C” fires involving live electrical equipment can be protected with CO2.

Areas of Use


CO2 is particularly useful for extinguishing fires in specific hazard areas or equipment where:

  • An inert, electrically non-conductive medium is essential or desirable. 
  • The cleanup or down-time of another medium would be detrimental or costly. 
  • Other mediums might contaminate solvents, coolants, or other products associated with the hazard being protected.

Some of the hazard types and equipment that can be satisfactorily protected with CO2 include:

  • Battery Rooms
  • Flammable Liquid Storage
  • Engine Test Cells
  • Printing Presses
  • Solvent Recovery Equipment
  • Record Storage
  • Wet Benches
  • Electric Generators
  • Coating Machines
  • Underfloor Areas
  • Fur Storage Vaults
  • Dust Collectors
  • Wave Solder Machines
  • Spray Booths
  • Ovens
  • Dip Tanks & Drain Boards
  • Motors
  • Switchgear Equipment
  • Transformer Vaults
  • Ducts
  • Hydraulic Pump Units

Areas of Non-Use

CO2 should NOT be used on fires involving the following materials:

  • Chemicals that contain their own oxygen supply such as: cellulose nitrate (old movie film) and gunpowder, which are capable of rapid oxidation in the absence of air. 
  • Reactive metals such as: Lithium, Sodium, Potassium, Magnesium, Titanium, Uranium, or Plutonium. 
  • Metal Hydrides such as: Sodium Hydride, Lithium Hydride, Calcium Hydride, Lithium Aluminum
    Hydride, and Sodium Borohydride.

While CO2 will not extinguish fires involving these products, it will not react dangerously with them or increase their burning rate. A CO2 system designed for Total Flooding will provide protection of adjacent combustibles when used in these situations. Local Application systems with their attendant high velocity and directed discharge should NOT be used for these applications.

Static Electricity

CAUTION: Where CO2 may be discharged into potentially explosive atmospheres. Electrostatic charging of non-grounded conductors may occur during the discharge of liquefied gases. These conductors may discharge to another object causing an electric spark of sufficient energy to initiate an explosion.

Personnel Safety

Extinguishing concentrations of CO2 create a health hazard to area personnel. High concentrations of CO2 will cause suffocation. In addition, fogging during and after discharge can limit visibility in protected areas. CO2 does not contain oxygen in any form or quantity and WILL NOT sustain life.


The following human reactions to CO2 have been documented:

  • At concentrations of 3 to 4% by volume in the atmosphere, the breathing rate increases and headaches may occur. 
  • At concentrations exceeding 9% by volume, personnel can lose consciousness within minutes. This is generally preceded by disorientation, visual disturbance, ringing in the ears, tremors, etc. 
  • At concentrations greater than 20% by volume, death is likely.

The above effects are important to note as inexperienced personnel may fail to think clearly and take proper action if suddenly exposed to relatively low concentrations of CO2.


Any person overcome by CO2 should be moved immediately to a location where plenty of fresh air is available and artificial respiration applied, as in a case of drowning. DO NOT use CO2 as a stimulant. Call a physician or take the patient to a hospital for examination. Persons rendered unconscious by exposure to CO2 can usually be revived without any permanent ill effects when promptly removed from a CO2 atmosphere.

Exposure

Direct contact with liquid CO2 or the dry ice particles associated with the agent discharge will cause severe frostbite burns to the skin. CO2 vaporizes quite rapidly; therefore, the hazard is generally limited to the immediate vicinity of the discharge nozzle(s).

Agent Migration

CO2 can drift into, and settle in adjacent spaces unless specific precautions are taken to prevent leakage from the protected space, and/or leakage into nearby areas. Such leakage can accumulate into dangerous concentration levels if left unattended. Consideration must be given to warning all personnel in the area of possible agent migration. A means of ventilating the CO2 from enclosed areas, pits, etc., shall be considered when designing a CO2 suppression system. Consult NFPA 12 for additional personnel safety guidelines. 

Typically, flooded hazards and low-lying areas must be well ventilated before personnel are allowed to re-enter the protected space(s). Under some circumstances, it may be necessary to provide self-contained breathing apparatus (SCBA) to all persons responsible for investigating the event. When all traces of the fire have been extinguished and the possibility of re-ignition eliminated, thoroughly ventilate the hazard to ensure that only fresh air is remaining in the protected space. When there is a question as to the presence of CO2 after a discharge, DO NOT ENTER. Rely on the fire department or other responsible authorities to determine when it is safe to re-enter.

1.4.3 SAFETY RECOMMENDATIONS
Safeguards MUST be provided to ensure the safety of personnel occupying areas in which the atmosphere could be made hazardous from the discharge of CO2. The following list taken from NFPA 12 contains safety
recommendations that we urge the installer to follow with each installation.

  • Provide open aisle ways and exit routes. Keep them clear and well marked at all times.
  • Provide emergency lighting and directional signs to ensure quick and safe evacuation.
  • Provide audible/visual alarms inside and outside all protected areas that operate immediately upon the detection of a fire condition. Delay the CO2 discharge and the actuation of door closing devices for a sufficient time period to allow evacuation of the affected area(s).
  • Provide ONLY outward swinging, self-closing doors at all exit points from the hazard area(s). Where such doors could be latched or secured, provide “panic” hardware.
  • Provide continuous alarms at the entrances to all protected spaces that will operate until the atmosphere has been returned to normal and the control panel has been reset.
  • Provide warning and instructional signs at all entrances to, and inside of, each protected space. These signs should inform persons inside, or entering into the protected space, that a CO2 system is protecting the area. These signs may also contain additional information or instructions pertinent to the conditions of the specific hazard.
  • Provide for the prompt discovery and rescue of any person(s) trapped or rendered unconscious in all protected areas. This is accomplished by having all affected areas searched by trained personnel equipped with the proper breathing and rescue equipment. Only personnel trained in its use and in rescue techniques including artificial respiration should perform this task.
  • Provide instructions and drills for all personnel within, or in the near vicinity of the protected area. This instruction should include all maintenance and construction personnel who may be brought into the area.  This training will ensure that the area personnel will respond correctly, should the CO2 system operate.
  • Provide a means of prompt ventilation of the protected area(s). Forced ventilation will often be necessary. Care must be taken to ensure that the CO2 atmosphere is dissipated and not merely moved to another location.
  • CO2 is much heavier than air and can collect in pits, cellars, and other areas that lie below the floor level of the protected space. Care must be taken when entering these areas after a discharge.
  • Provide all other steps and safeguards that a careful study of each CO2 system application indicates are necessary to prevent injury or death.

Information provided from Fike Carbon Dioxide Manual Rev. 8/06

Micromist (Water Mist)

Introduction

Fike Corporation is proud to present the Fike Micromist Fire Suppression System. The Fike Micromist System is a self-contained, single fluid, pre-engineered, water mist fire suppression system for total compartment protection of machinery spaces and gas turbine spaces.

Micromist is an intermediate pressure, 175 to 500 psi (11,207 to 3,447 kPa), system that uses a fine water spray to extinguish a fire. The fine spray extinguishes a fire by cooling the flame and fire plume, displacing oxygen with water vapor, and reducing the amount of radiant heat.

Micromist systems are designed, and have been tested, for use in protecting flammable liquid (Class B) processes and incidental combustible (Class A) materials. Micromist applications include, but are not limited to, the following:

  • Compartmentalized gas turbines
  • Engine test cells
  • Generator rooms
  • Machinery spaces with incidental storage of flammable liquids
  • Oil pumps
  • Lubrication skids
  • Oil reservoirs
  • Diesel emergency rooms
  • Fuel filters
  • Dipping, electrostatic coating, or cleaning processes using flammable liquids
  • Gear boxes
  • Drive shafts
  • Engine driven generators
  • Chemical processes
  • Flammable or combustible liquid pumps, piping, or containers under pressure such as may be used with hydraulic pumping equipment

System Limitations

The following limitations apply to the use and application of Fike Micromist Systems:

1. Micromist systems are capable of protecting hazards with maximum volumes not exceeding 9,175 ft3 (260 m3), with a maximum ceiling height of 16 ft. (4.9 m).

2. The following items pertain to the hazard enclosure:

• The protected hazard should be equipped with: Automatic door closures, a ventilation system, and
automatic fuel shutdown.

• Lubrication supply should be shutoff as soon as possible.
• It is recommended that all, non-emergency, electrical power to the protected space be interrupted at the time of system discharge.

3. Micromist skid must be installed in a location where the ambient temperature is maintained within +40°F to +130°F (4.4°C to 54.4°C) and must be protected from inclement weather, mechanical, chemical, or other damage.

4. The Micromist System shall not be used for direct application to materials, or products, that react with water to produce violent reactions or significant amounts of hazardous products. These materials include:

• Reactive metals (e.g. Sodium, Potassium, Magnesium, Titanium, Lithium, Uranium, and Plutonium)
• Metal Alkoxides (e.g. Sodium Methoxide)
• Metal Amides (e.g. Sodium Amide)
• Carbides (e.g. Calcium Carbide)
• Halides (e.g. Benzoyl Chloride)
• Hydrides (e.g. Lithium Aluminum Hydride)
• Oxyhalides (e.g. Phosphorus Oxybromide)
• Silanes (e.g. Trichlormethyl Silane)
• Sulfides (e.g. Phosphorus Pentasulfide)
• Cyanates (e.g. Methylisocyanate)
• The Micromist System SHALL NOT be used for direct application to liquefied gases at cryogenic temperatures, such as liquefied natural or propane gases, which boil violently when heated by water.

5. Micromist Systems CAN be used to protect an area having a flammable liquid present, provided it is a Flammability Class of 1, 2, or 3 as defined by the Fire Protection Guide to Hazardous Materials, 2001 Edition. Examples of Class 1, 2, and 3 flammable liquids are:

• Fuels such as #2 Diesel Fuel, Gasoline, Kerosene, Mineral Spirits, and Jet Fuels (4, 5, & 6)
• Oils such as Lubricating, Hydraulic Oil & Fluid, Transformer, and Crude.

6. Liquids with a flash point below 73°F (22.8°C) and a boiling point below 100°F (37.8°C) are Class 1A liquids that CANNOT be protected with a Micromist System. Liquids with a flash point above 73°F (22.8°C) that are categorized as Class 1B, 1C, 2, or 3 (A or B) as defined by the Fire Protection Guide to Hazardous Materials, 2001 Edition, CAN be protected with a Micromist System.

7. Micromist Systems CANNOT be used to protect an area with a Class 4 flammable liquid as defined by Fire Protection Guide to Hazardous Materials, 2001 Edition. Examples of Class 4 flammable liquids are: Methane, Propane, Natural Gas, Butane, and Hydrogen.

• Exception: Natural Gas and Propane driven Turbine Generator units may be protected providing the fuel source is shut down prior to discharge.

8.  The Micromist System provides 10 minutes of active protection for Machinery Spaces. For Gas Turbine Spaces, the Micromist System provides 20 minutes of active protection.

9.  Micromist Systems can be used to protect hazards having a range in temperature from +40°F to +325°F (+4.4°C to +162.7°C).

Operating Principles

Water is an outstanding fire suppression agent due to its high heat capacity and latent heat of vaporization. The Micromist nozzles use a plate to slice the small jets of water that flow through the nozzle orifice. The resulting water mist contains a variety of droplet sizes. The larger droplets provide the necessary energy and momentum to carry the smaller droplets to the base of the fire where the mist vaporizes and extinguishes the fire. The simple theory behind this development is a large amount of small droplets have a greater surface area than the same number of large droplets, therefore absorbing more heat.

Water mist systems extinguish fires using the following basic principles:

  • Cooling – As the mist is converted into vapor it removes heat from the fire source.
  • Oxygen displacement – As the water mist turns to steam it expands approximately 1,700 times, forcing oxygen away from the flame front, thus denying it the oxygen necessary to support combustion. (localized inert environment)
  • Wetting – Primarily for incidental class A fires; wetting of the surface helps extinguish the fire as well as contain it.

The Micromist System extinguishes a fire by delivering a controlled, cyclic supply of water to a network of nozzles. Upon activation, and throughout the active protection period, the Fike Cheetah Control Panel sends signals to both high and low pressure side solenoids, to provide and control the required cyclic supply of water. The Nozzle Assemblies receive the water through the pre-engineered piping network. The nozzles create a fine water mist by the impingement of the water on the edge of a plate. The fine mist produced is directed into the protected space by nozzle placement.

Personnel Safety


For fire situations, suitable safeguards SHALL be provided to ensure prompt and complete evacuation of, and prevent entry into, hazardous atmospheres and also to provide for prompt rescue of persons trapped within a protected space. Safety considerations, such as personnel training, caution and/or advisory warning signs, discharge alarms and lights, self-contained breathing apparatus (SCBA), evacuation plans, and fire drills shall all be carefully planned and implemented.

Definitions


Fike recognizes the difference between pipe and tube; however, for ease of understanding, the term “pipe” will
be used to describe both pipe and tubing.


Cycle - A single on/off sequence of the solenoid.
Elevation Change - The net difference in elevation from the water outlet on the Water Storage Container to the
most remote nozzle.
Node - A section of the piping network which supplies water to a certain number of nozzles, and includes all
fittings in that section. Also includes the tee supplying the pipe section.
Nozzle Flow - The number of nozzles being supplied by a section of pipe.
Potable Water - Water that is fit to drink with respect to particulate and dissolved solids.
Pressure Drop - The amount of pressure lost due to elevation change, nozzle output, fittings, and distance of
the most remote nozzle.
Shot - A series of cycles, where the type of space being protected determines the quantity of cycles.

Information provided from Fike Micromist Manual Rev. 2/99

Special Hazard System Testing

Clean Agent Systems (Including Ecaro-25, FM-200, ProInert, Inergen)

NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems Inspection Requirements

System Component Test Frequency
System Test

Annually

Agent quantity and Pressure of refillable containers Semi-Annually
Pressure indicators Semi-Annually
Cylinder visual inspection (non-discharged) 5 years
Hose (Visual) Annually
Hose (Test) 5 years
Enclosure Inspection Annually
Electrical Components Per NFPA 72

Carbon Dioxide System Testing

High Pressure Carbon Dioxide Systems

NFPA 12 Carbon Dioxide Extinguishing Systems Inspection Requirements

System Component Test Frequency
Systems operational condition 30 days
Hose (Test) 5 years
Cylinder (Weight) Semi-Annually
Cylinder (Hydrostatic Test) 5 years
Liquid Level Gauges Weekly
Electrical Components Per NFPA 72


shadow bottom